Wind Loads
The information presented here follows the '94 UBC guidelines 1613 through 1623 and the '97 UBC 1615-1625. These requirements may be
applied to buildings with H/W < 5 and H < 400 ft. In addition, for one or two story masonry buildings in seismic
zones 0, 1, or 2 with basic wind speeds from 80 - 110 mph, refer to the Appendix Chapter 21 of the UBC titled
"Prescriptive Masonry Construction in High Wind Areas".
Topic Directions:
Two class days will be devoted to this wind load topic and related project activities. To complete this topic you need to:
- Study the four sets of on-line lecture notes.
- Complete the reading assignment.
- Come to each class period prepared to discuss the following material:
- Day 1 - Wind pressure, building stability, and drift.
- Day 2 - Example and Project.
- Complete the various problem assignments and submit
for grading only those assignments designated as such:
- Wind pressure and stability.
- Analysis: Submit on day 3.
- Complete the wind load phase of the design project and submit as directed in the project area of this class.
On-Line Lecture:
Reading Assignment:
- Breyer, Chapter 2, Sections 2.9 - 2.11.
- Breyer, Chapter 3, Sections 3.3 - 3.5.
Problem Assignment:
Complete the following problem sets using the calculation procedures outlined in the lecture notes and by Breyer.
- Wind Pressure: Breyer, problems 2.19, 2.20.
- Stability: Breyer, problem 2.18
- Analysis: Breyer, problem 3.9 (except building is partially enclosed).
Design Project Assignment:
Go to the Project area of this class and read the wind load directions.
|