Wind Loads
Example
Develop the applicable wind forces for a one-story, box-type industrial
complex located in Southern California, in a suburban area with roof D =
12 psf and 16" o.c. partially grouted CMU walls.
- Design pressure for primary LFRS:
For this example, the pressure coefficients are the same regardless
of load direction.
P = Ce Cq qs Iw
qs Þ V = 70 mph (Figure
16-1, UBC '97)
qs = 12.6 (UBC '97 Table 16-F)
Iw = 1.0 (UBC '97 Table 16-K)
| Ce Þ Exposure
B Þ |
{ |
.62 |
(0 - 15') |
(UBC '94 Table 16-G) |
| .67 |
(20') |
| CqÞ |
Method 1
(Table 16-H) |
Þ |
{ |
.8 windward |
Assuming » flat roof
and closed building. |
| -.5 leeward |
| -.7 roof |
The resulting pressure diagram for wind loading in the transverse direction:

- Diaphragm Loading:
- Showing transverse loading here.
- Consider a 1' width of wall that is simply supported at foundation
and roof.
- Examine the normal wall load effect on the supporting diaphragm:
- Since the diaphragm must support both, simultaneously, the
inward and outward pressures, model these effects as a resultant
pressure.

- The roof diaphragm must resist 125.4 lb/ft (or, in other words,
each foot of wall produces a force of 125 lbs on the diaphragm.)

- Diaphragm to shear walls for flexible diaphragms:
Diaphragm Plan View:

In this example, the shear wall at each end must resist a resultant
load of 7837.5 lbs.

- Upon development of the shear wall loads, examine shear wall drift
and overturning.
- Shear wall drift:
- L/h = 66/17 = 3.88, drift dominated by shear deflection.
- Therefore during wall design, ensure that D
» 1.2 P h / G A £
.0025 h
- Overturning (OM)
- Since this is a shear wall building, every shear wall should
be checked for OM.
- Check all shear walls, in lieu of an overall building OM check
(In other words, if the shear walls are adequate then the overall
building is adequate. But, remember that overall building stability
does not ensure that all shear walls are ok).

RM = Resisting Moment
RM = 87120 (33) = 2,874,960 ft-lbs
OM = Overturning Moment
OM = 7837.5(17) = 133,240 ft-lbs
- If the shear wall supported a significant % of the roof framing,
then a portion of roof uplift should be included in OM. Likewise,
a portion of the roof dead load should be included in RM.
- 2 / 3 RM = 1,916,640 > > OM
- No special anchorage required for the shear wall, which is
typical for masonry walls that support wood roof systems. (This
is not, however, true for all wood buildings with wood shear
walls. Very often, these lightweight walls will need special
hold down anchors to resist the overturning potential.)
- Lateral forces normal to the wall.
- In addition to acting as shear walls, these walls must be designed
to resist forces acting perpendicular to them.
- These perpendicular forces do not come from the primary LFRS analysis
as shown in step 1. Develop these forces by considering localized,
higher loads taken on portions of the building as reflected in Cq.
- A careful reading of '97 UBC Table 16-H indicates two load cases
here.
- One for all structures and the other for enclosed and unenclosed
structures.
- For outward (negative) forces, use Cq/Ce based on mean roof
heights.
- For inward (positive) forces, use Cq/Ce based on the actual
height of the element.

- Repeat wind load development and distribution for wind in longitudinal
direction.
|